Current

Input.

Voltage

Input.

High Precision Shunt

Resistor

Eliminates secondary

current transformers and

improves linearity.

State-of-the-art

Electromagnetic Noise

Suppression Circuitry.

Ensures signal integrity even in harsh EMC environments.

Zero Crossing

Detector.

Allows high resolution

line-frequency measurement.

Interface to

Tiger Meter.

Differential Voltage

Divider.

Safe operation for direct connection to phase-tophase voltages.

16-bit Dual Channel

Synchronous A/D

Converter.

Delivers unmatched

accuracy and performance.

Math Co-processor.

Offloads work from Tiger

320 processor, leaving it free to perform advanced automation and control

functions.

IW04 (600V, 1 Amp) IW05 (600V, 5 Amp)

IW04_IW05 smart module manual (NZ322)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 1

Programming Quick Start Guide

Connector Pinouts

Figure 1 Single Phase, 2-wire Configuration

Figure 2 Single Phase, 3-wire Configuration

Smart Setup Registers

The meter uses three smart setup registers to configure all smart input modules. Input modules IW04/5 require only smart register 1 to be set up. These modules produce four output registers.

One of these registers can be transferred to Channel 1 via Code 2, the same or another register to Channel

2 via Code 4, the same or another register to Channel 3 via Code 5, and the same or another register to Channel 4 via Code 6.

Input modules IW01/2/4/5 have a zero crossing detector that is available for direct line-frequency measurement in Channel 2. The following resolution settings can be selected in Code 4:

0 to 99.999 Hz, 0.001 Hz resolution.

Set Code 4 to [30X].

0 to 999.99 Hz, 0.01 Hz resolution.

Set Code 4 to [31X].

Note, the direct line-frequency measurement setting for channel 2 is a hard-wired option and, if selected, means channel 2 is not available for selecting an output register.

for

Line-frequency

CH2 ONLY

Figure 3 Smart Input Module IW04/5 Signal Flow Diagram

IW04_IW05 smart module manual (NZ322)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 2

Input Signal

Programming Procedures

The following programming procedures cover all the steps required to configure smart input module IW04/05 as follows:

Figure 4 IW04/5 Smart Setup Registers Operational Flow Diagram

Channel 1 to display current (I rms).

Channel 2 to display direct line-frequency measurement.

Channel 3 to display voltage (V rms).

Channel 4 to display power usage (kW).

Steps 1 to 6 describe how to select the current gain setting through smart register 1.

Steps 7 to 13 describe how to select the output registers for channels 1, 2, 3, or 4 as required.

Steps 14 to 16 describe how to select line-frequency for channel 2.

buttons at the same time to enter the main programming mode.

This setting enters the smart register 1 code setup menu.

Note the output register map is different for each smart input module.

This menu provides settings unique to input modules IW01 to IW04.

This takes you back to the Code 2 menu.

Note the output registers in the 3rd digit are specific to IW04/5. These registers vary for each different smart input module.

The next step is to select the appropriate output register from the output register map for a selected channel.

Continued on next page

IW04_IW05 smart module manual (NZ322)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 3

Select a Channel

Select the output register for the required channels

button at the same time again to re-enter the main programming mode.

9 To select channel 1, set Code 2 to [X7X]. Select the required processing rate for CH1 in the 1st

digit and the required register map settings in the 3rd digit.

CH1

To select channel 2, enter Code 4 and select the required register map settings for CH2 in the 2nd digit.

Note the output register map is different for each smart input module type.

CH2

Note, If you require the direct line-frequency measurement setting, channel 2 will not available for selecting an output register.

To select channel 3, enter Code 5 and select the required post processing settings for CH3 in the 1st digit and the required register map settings in the 3rd digit.

To select channel 4, enter Code 6 and select the required post processing settings for CH4 in the 1st digit and the required register map settings in the 3rd digit.

CH4

buttons at the same

Note the output register map is different for each smart input module type.

IW04_IW05 smart module manual (NZ322)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 4

Select the Line Frequency Select the line frequency on Channel 2

button at the same time again to re-enter the main programming mode.

Set Code 4 to [3X0]. Select the required line frequency measurement in the 2nd digit.

Note, the direct line-frequency measurement setting for channel 2 is a hard-wired option and, if selected, means channel 2 is not available for selecting an output register.

DI-503 WHITE TRIM 2/May/02

CH2

Example Single Phase Power Module Setup Procedure

Our customer has a powerful single phase motor connected to the 120 V rms supply. The motor can draw up to 200 A rms under full load. As part of the supervisory programme, the owner requires to monitor the line voltage, current draw, and resultant power usage simultaneously.

A Tiger 320 Series triple display meter is installed to display:

Channel 1:

Current (I rms) on the top (primary display).

Channel 3:

Voltage (V rms) on the middle display.

Channel 4:

Power usage (kW) on the bottom display.

CH1

CH3

Channel 2:

Configured to read the line frequency at 0.01 Hz resolution (displayable in the view mode).

Because there is a 5 A rms maximum current limit on smart power module IW02, a 200:5 current transformer is used to sense the load current.

CH4

The meter is calibrated at the factory to the following default settings with a scale factor of 1 and an offset of 0:

30,000 counts for 5 A rms.

1000 counts for 100 V rms.

10,000 counts for 500 W.

To accomodate the customers specifications, the offsets remain at 0, but the scale factors must be adjusted to display (See Recalibration Procedures on Page 6):

20,000 counts for 200 A on CH1.

1,200 counts for 120 V on CH3.

24,000 counts for 24 kW on CH4.

The new scale factors are calculated as follows:

1 CH1 Scale Factor

Our 200 A load is reduced to 5 A to suit the smart input modules maximum current limit by passing it through a 200:5 current transformer (CT).

The original factory setting was 30,000 counts for the maximum load.

We now want to display 20,000 counts for the same load. Therefore, the scale factor is calulated as:

CH1 Scale Factor =

20,000

30,000

= 0.666 (I rms)

2 CH3 Scale Factor

Our original factory setting for the 100 V line voltage was 1,000 counts. Applying a new line voltage of

120 V to the original settings for CH3 displays 1,200 counts on the meter. Therefore, no adjustment is necessary and the scale factor remains unchanged at 1.0.

3 CH4 Scale Factor

Our original factory setting for the power reading on CH4 is:

5 A load & 100 V line voltage = 500 W over 10,000 counts

Our load has now increased to 200 A, which is passed through a 200:5 CT effectively retaining a 5 A load.

Our line voltage has increased to 120 V displayed over 1,200 counts. This means we now have:

5 A load (actual 200 A) & 120 V line voltage = 600 W over 12,000 counts

We wish to double the resolution of the power reading on the display to 24,000 counts for the maximum load. Therefore, the scale factor is calculated as:

CH4 Scale Factor =

24,000

12,000

= 2.0

IW04_IW05 smart module manual (NZ322)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 5

Recalibration Procedures

The following recalibration procedures describe how to recalibrate the scale factors for CH1, CH3, and CH4 if they are different from the Texmate factory default settings. See the new scale factor calculations on the example on Page 5.

buttons at the same time to enter the main programming mode.

The display toggles between [CAL] and [101].

The display toggles between [OFF_1] and [0.0].

The COS value does not require any user scaling. However, make sure that the appropriate channel scaling register is set to 1.0 and the offset set to 0.

5 Press the P button.

The display toggles between [SCA_1] and [1.0000].

Example

7 Press the P button once to return to the calibration mode.

The display toggles between [CAL] and [101].

The display enters the offset and scale factor setting menu for CH3.

Repeat Steps 4 to 6, but set the Scale Factor for CH3 to the new settings.

Example

10 Press the P button once to return to the calibration mode.

The display toggles between [CAL] and [103].

The display enters the offset and scale factor setting menu for CH4.

Example

buttons at the same time to return to the operational display.

The scale factor for CH1, CH3, and CH4 has now been reset.

IW04_IW05 smart module manual (NZ322)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 6

Single Phase Measurement and Control

It is no longer necessary to use combinations of transducers to achieve a power measurement and control system.

A Texmate Tiger 320 Series DI-503 meter, installed with a single-phase power input module, calculates and displays volts, amps, Hz, watts, watt hours, and power factor from a single-phase 2 or 3-wire voltage and current input.

SINGLE PHASE MEASUREMENT AND CONTROL

The optional relay, analog and serial outputs can be configured from all the above parameters to interface with a control or alarm system.

TIGER 320 SERIES DI-503 TIGER 320 SERIES DI-503

OPTIONS

Up to 6 super smart relay outputs, digitally

programmable upper and lower limits.

Programmable deviation mode, hysteresis mode, latch

ON or latch OFF.

Built-in super smart timers on each setpoint.

Programmable DOM to eliminate nuisance tripping.

Power ON inhibit to avoid tripping during power up.

Dual 4-20 mA or 0-10 V, 16-bit analog output.

RS-232 or RS-485.

DeviceNet / ModBus.

Direct serial printer output.

Data logging with real-time clock.

DISPLAY AND CALCULATE

Voltage (R.M.S.).

Current (R.M.S.).

Frequency.

Watts, kilowatts.

Watt hours, kilowatt hours.

Power factor monitoring

for precise load sensing.*

MULTIPLE TRANSDUCERS NO LONGER REQUIRED

* APPLICATION CONCEPT

Power factor gives an accurate measure of load change, particularly at low to medium loads, where current is dominated by it's magnetizing element. Where prompt action is required the optional relays in the Tiger 320 Series meter can be used for protection against broken belts, pump cavitation, conveyor stalling and general overloads.

IW04_IW05 smart module manual (NZ322)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 7

1934 Kellogg Ave., Carlsbad, CA 92008 Tel: 1-760-598-9899 USA 1-800-839-6283 1-800-TEXMATE Fax: 1-760-598-9828 Email: [email protected] Web: www.texmate.com

IW04_IW05 smart module manual (NZ322)

Texmate, Inc. Tel. (760) 598-9899 www.texmate.com

Page 8

About TexMate

Texmate is an American manufacturer of high durability industrial grade panel meters, bar graphs, and transducers. Texmate's meters are frequently equipped with relays and various signal outputs for industrial automation applications and are known for their extremely long service life.